OMRON Power Supplies - S8JX-P
Model Numbers | Power Supplies – S8JX-P
Model Number Structure
Model Number Legend
Note: Not all combinations are possible. Refer to List of Models in Ordering Information below.
Note: Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON
representative for details.
Ordering Information
List of Models
Note: For details on normal stock models, contact your nearest OMRON representative.
DIN Rail-mounting
Configuration | Input voltage | Power ratings | Output voltage (VDC) | Output current | Built-in fan | Model |
---|---|---|---|---|---|---|
Covered Power Supplies |
100 to 240 VAC (free) (80 to 370 VDC *) |
300 W | 5 V | 60 A | Yes | S8JX-P30005CD |
12 V | 27 A | S8JX-P30012CD | ||||
24 V | 14 A peak current 16.5 A (200 VAC) |
S8JX-P30024CD | ||||
48 V | 7 A | S8JX-P30048CD | ||||
600 W | 5 V | 120 A | S8JX-P60005CD | |||
12 V | 53 A | S8JX-P60012CD | ||||
24 V | 27 A peak current 31 A (200 VAC) |
S8JX-P60024CD | ||||
48 V | 13 A | S8JX-P60048CD |
* The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Front-mounting
Configuration | Input voltage | Power ratings | Output voltage (VDC) |
Output current | Built-in fan | Front- mounting bracket |
Model |
---|---|---|---|---|---|---|---|
Covered Power Supplies |
100 to 240 VAC (free) (80 to 370 VDC *) |
300 W | 5 V | 60 A | Yes | Provided | S8JX-P30005C |
12 V | 27 A | S8JX-P30012C | |||||
24 V | 14 A peak current 16.5 A (200 VAC) |
S8JX-P30024C | |||||
48 V | 7 A | S8JX-P30048C | |||||
600 W | 5 V | 120 A | S8JX-P60005C | ||||
12 V | 53 A | S8JX-P60012C | |||||
24 V | 27 A peak current 31 A (200 VAC) |
S8JX-P60024C | |||||
48 V | 13 A | S8JX-P60048C | |||||
300 W | 5 V | 60 A | No | S8JX-P30005N | |||
12 V | 27 A | S8JX-P30012N | |||||
24 V | 14 A peak current 16.5 A (200 VAC) |
S8JX-P30024N | |||||
48 V | 7 A | S8JX-P30048N | |||||
600 W | 5 V | 120 A | S8JX-P60005N | ||||
12 V | 53 A | S8JX-P60012N | |||||
24 V | 27 A peak current 31 A (200 VAC) |
S8JX-P60024N | |||||
48 V | 13 A | S8JX-P60048N |
* The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
DIN Rail (Order Separately)
End Plate
Model |
---|
PFP-M |
Note: 1. Use a metal DIN Rail when mounting the S8JX-P to a DIN Rail.
2. If the Unit may be subjected to sliding to either side, attach an End Plate (model PFP-M) on each side of the Unit.
Terminal Cover (Order Separately)
Terminal Cover model | Applicable Power Supply and applicable location |
---|---|
S82Y-JX-C4P1 | S8JX-P 300 W/600 W output side |
S82Y-JX-C5P1 | S8JX-P 300 W/600 W input side |
Replacement Fan (sold separately)
Product | Model |
---|---|
Replacement fan unit for 300-W models | S82Y-JXP30FAN |
Replacement fan unit for 600-W models | S82Y-JXP60FAN |
Specificaitons | Power Supplies – S8JX-P
Ratings, Characteristics, and Functions
Input specification | 100 to 240 V input | ||||
---|---|---|---|---|---|
Power ratings *1 | 300 W | 600 W | |||
Efficiency | 5 V Models | 75% min. | 76% min. | ||
12 V Models | 77% min. | 76% min. | |||
24 V Models | 79% min. | 78% min. | |||
48 V Models | 78% min. | 79% min. | |||
Input | Voltage *2 | 100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *8) | |||
Frequency *2 | 50/60 Hz (47 to 63 Hz) | ||||
Current *3 |
100 V input | 4.5 A max. | 8.7 A max. | ||
200 V input | 2.2 A max. | 4.3 A max. | |||
Power factor | 0.9 min. | ||||
Harmonic current emissions | Conforms to EN61000-3-2 | ||||
Leakage current *3 |
100 V input | 0.5 mA max. | |||
200 V input | 1 mA max. | ||||
Inrush current (for a cold start at 25 °C) *3 |
100 V input | 17.5 A max. | |||
200 V input | 35 A max. | ||||
Output *4 |
Voltage adjustment range *5 | -10% to 15% (with V. ADJ) (5 V, 48 V models: ±10%) | |||
Ripple *3 | 3% (p-p) max. (5 V) *12 2% (p-p) max. (12 V) *12 2% (p-p) max. (24 V or 48 V types) |
||||
Input variation influence | 0.4% max. | ||||
Load variation influence | 0.8% max. (0 to 100% load, rated input voltage) | ||||
Temperature variation influence | 0.05%/ °C max. | ||||
Startup time | 1,000 ms max. | ||||
Hold time *3 | 20 ms min. | ||||
Addi- tional func- tions |
Overload protection *6 | 105% to 160% of rated load current, voltage drop, intermittent, automatic reset. |
|||
Overvoltage protection *7 | Yes | ||||
Overheat protection | Yes | ||||
Parallel operation | Yes (up to 5 Power Supplies) | ||||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | ||||
Remote sensing | Supported | ||||
Remote control | Supported | ||||
Alarm detection indication | Yes (color: red) | ||||
Alarm output | Provided, open-collector output, 30 VDC max, 50 mA max. | ||||
Other | Ambient operating temperature | Refer to the derating curve in Engineering Data on Catalog. (with no icing or condensation). |
|||
Storage temperature | – 25 to 75 °C (with no icing or condensation) | ||||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | ||||
Dielectric strength | 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 100 mA) 100 VAC for 1 min. (between all outputs and RC terminals; detection current: 100 mA) 500 VAC for 1 min. (between all outputs and ALM terminals; detection current: 20 mA) |
||||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC |
||||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions |
||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions *10 | ||||
Output indicator | Yes (Color: Green) | ||||
EMI | Conducted Emissions *3 |
Conforms to EN 55011 Group 1 Class B and based on FCC Class B *11 | |||
Radiated Emissions | Conforms to EN 55011 Group 1 Class B *11 | ||||
EMS | Electrostatic Discharge |
Conforms to EN61000-4-2 | |||
Radiated Electromagnetic Field |
Conforms to EN61000-4-3 | ||||
Electrical Fast Transient/Burst |
Conforms to EN61000-4-4 | ||||
Surge | Conforms to EN61000-4-5 | ||||
Conducted Disturbance |
Conforms to EN61000-4-6 | ||||
Voltage Dips/Short Interruptions |
Conforms to EN61000-4-11 | ||||
Approved standards *8 | UL UR: UL 508 (Recognition) *13 UL Listed: UL508 (Listing) *14 UL UR: UL 62368-1 (Recognition) |
||||
cUR: CSA C22.2 No.107.1, CSA C22.2 No. 62368-1 | |||||
EN/VDE: EN50178 (= VDE 0160) Over voltage category III, EN 62368-1 (Terminal block: Based on DIN 50274 (VDE 0660-514)) |
|||||
SEMI | SEMI F47-0706 (200-VAC input) | ||||
Weight | 1,200 g max. *9 | 1,800 g max. *9 |
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may notstart. Refer to Overload Protection on Catalog.
*2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internaltemperature of the Power Supply may result in ignition or burning. *3. Rated input voltage: 100 or 200 VAC at 100% load.
*4. Output characteristics: Specified at power supply output terminals.
*5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the outputvoltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.
*6. For details, refer to Overload Protection on Catalog.
*7. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*8. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
*9. The weight is of the type without a mounting bracket.
*10.S8JX-P600[][]CD: 100 m/s2
*11.The noise value will vary depending on wiring methods and other characteristics. 300-W/600-W models conform to Class B with an aluminum plate set under the product. For the 300-W 5V and 600-W 5V and 12V models, insert a noise filter (TDK-Lambda RSEN-2016) in the input line.
*12.Measurement method conform to RC-9131A of the JEITA standards. For details, refer to “Ripple Noise Voltage” on Catalog.
*13.Applicable to the 300-W/600-W 5V and 12V models
*14.Applicable to the 300-W/600-W 24V and 48V models
Dimensions | Power Supplies – S8JX-P
(Unit: mm)
Front-mounting Models
S8JX-P300[][]C (300 W)
S8JX-P300[][]N (300 W)
S8JX-P600[][]C (600 W)
S8JX-P600[][]N (600 W)
DIN Rail-mounting Models
S8JX-P300[][]CD (300 W)
Note: Use a metal DIN Rail when mounting a 300-W model to a DIN Rail.
S8JX-P600[][]CD (600 W)
Note: Use a metal DIN Rail when mounting a 600-W model to a DIN Rail.
DIN Rail (Order Separately)
End Plate
Note: 1. Use a metal DIN Rail when mounting the S8JX-P to a DIN Rail.
2. If the Unit may be subjected to sliding to either side, attach an End Plate (model PFP-M) on each side of the Unit.
Features | Power Supplies – S8JX-P
- Limits for harmonic current emissions (conforms to EN61000-3-2)
- Conforms to EMI EN55011 Class B
- Applicable to input free voltage: 100 to 240 VAC
- Extended DC input voltage range: 80 to 370 VDC
- * DC input is not subject to EC directives and safety standards.
- Easy mounting: Front-mounting bracket type and DIN-Rail mounting type are included as standard with the product.
- Safety standards
- UL508/62368-1, cUL CSA C22.2 No.107.1, cUR CSA C22.2 No.62368-1
- EN50178 (=VDE0160) Over voltage category III EN62368-1
- High capacity application-covered functions are included as standard with the product.
- Alarm detection function, Remote control function, Remote sensing function
Properties | Power Supplies – S8JX-P
Power Supplies | S8FS-G | |
---|---|---|
Output | 24 VDC | |
Input | 100 – 240 VAC | |
Rated voltage | 300 W | |
current | 7 – 60 A | |
Size | Front-mounting (W x L x D) (mm) |
77.6 x 217.3 x 124.3 (S8JX-P300[][]C (300 W)) |
71 x 165 x 92 (S8JX-P300[][]N (300 W)) | ||
116.6 x 217.3 x 113.5 (S8JX-P600[][]C (600 W)) | ||
110 x 164.8 x 92 (S8JX-P600[][]N (600 W)) | ||
DIN-rail | 110 x 164.8 x 92 (S8JX-P600[][]N (600 W)) | |
116.6 x 222.8 x 110.8 (S8JX-P600[][]CD (600 W)) | ||
Weight (g) | 1200 – 1800 |