OMRON Safety Door Switches – D4BS series
Model Numbers | Safety Door Switches – D4BS series
Switches (Operation Keys are sold separately.)
Consult with your OMRON representative when ordering any models that are not listed in this table.
Type | Mounting direction | Conduit outlet | 1NC/1NO (Slow-action) | 2NC (Slow-action) | |
---|---|---|---|---|---|
1-conduit type | Front-side mounting | Pg13.5 | D4BS-15FS | D4BS-1AFS | |
G1/2 | D4BS-25FS | D4BS-2AFS | |||
M20 | D4BS-45FS | D4BS-4AFS |
Operation Keys
Type | Model | |
---|---|---|
Horizontal mounting | D4BS-K1 | |
Vertical mounting | D4BS-K2 | |
Adjustable mounting (Horizontal) | D4BS-K3 |
Specifications | Safety Door Switches – D4BS series
Standards and EC Directives
Conforms to the following EC Directives:
・Machinery Directive
・EN50041
・EN ISO 14119
・EN 60204-1
Certified Standards
Certification body | Standard | File No. |
---|---|---|
TÜV Rheinland | EN60947-5-1 (certified direct opening) GS-ET-15 |
Consult your OMRON representative for details. |
UL | UL508 | E76675 |
CSA | CSA C22.2 No. 14 | LR45746 |
CQC (CCC) | GB/T 14048.5 | Consult your OMRON representative for details. |
Certified Standard Ratings
TÜV (EN60947-5-1), CCC (GB/T 14048.5)
Utilization category | AC-15 |
---|---|
Rated operating current (Ie) | 0.75 A |
Rated operating voltage (Ue) | 240 V |
Note: Use a 10 A fuse type a gI or gG that conforms to IEC60269 as a short-circuit protection device.
UL/CSA (UL508, CSA C22.2 No. 14) (A600)
Rated voltage | Carry current | Current (A) | Volt-amperes (VA) | ||
---|---|---|---|---|---|
Make | Break | Make | Break | ||
120 VAC 240 VAC 480 VAC 600 VAC |
10 A | 60 30 15 12 |
6 3 1.5 1.2 |
7,200 | 720 |
Characteristics
Interlock type | Type 2 (EN ISO 14119) | |
---|---|---|
Coding level | Low level coded (EN ISO 14119) | |
Degree of protection *1 | IP67 (EN60947-5-1) | |
Durability *2 | Mechanical | 1,000,000 operations min. |
Electrical | 500,000 operations min. (10 A resistive load at 250 VAC) | |
Operating speed | 0.1 m/s to 0.5 m/s | |
Operating frequency | 30 operations/minute max. | |
Direct opening force *3 | 19.61 N min. (EN60947-5-1) | |
Direct opening travel *3 | 20 mm min. (EN60947-5-1) | |
Contact resistance | 25 mΩ max. | |
Rated insulation voltage (Ui) | 600 V (EN60947-5-1) | |
Rated frequency | 50/60 Hz | |
Protection against electric shock | Class I (with ground terminal) | |
Pollution degree (operating environment) | 3 (EN60947-5-1) | |
Impulse withstand voltage (Uimp) (EN60947-5-1) |
Between terminals of same polarity | 4 kV |
Between terminals of different polarity |
||
Between each terminal and ground | ||
Insulation resistance | 100 MΩ min. (at 500 VDC) between terminals of same or different polarity, between each terminal and ground, and between each terminal and non-current-carrying metal part |
|
Contact gap | 2 × 2 mm min. | |
Vibration resistance | Malfunction | 10 to 55 Hz, 0.65 mm single amplitude |
Shock resistance | Destruction | 1,000 m/s2 min. (IEC68-2-27) |
Malfunction | 300 m/s2 min. (IEC68-2-27) | |
Conditional short-circuit current | 100 A (EN60947-5-1) | |
Conventional enclosed thermal current (Ithe) | 20 A (EN60947-5-1) | |
Ambient operating temperature | -40 to 80°C (with no icing) | |
Ambient operating humidity | 95% max. | |
Weight | Approx. 285 g (D4BS-15FS) |
Note: The above values are initial values.
*1. The degree of protection is tested using the method specified by the standard (EN60947-5-1). Confirm that sealing
properties are sufficient for the operating conditions and environment beforehand. Although the switch box is
protected from dust, oil, or water penetration, do not use the D4BS in places where dust, oil, water, or chemicals may
enter through the key hole on the head, otherwise Switch damage or malfunctioning may occur.
*2. The durability is for an ambient temperature of 5 to 35°C and an ambient humidity of 40% to 70%. Contact your
OMRONsales representative for more detailed information on other operating environments.
*3. These figures are minimum requirements for safe operation.
Dimensions | Safety Door Switches – D4BS series
(Unit: mm)
Note: Unless otherwise specified, a tolerance of ±0.4 mm applies to all dimensions.
Switches
1-conduit type
D4BS-1[]FS
D4BS-2[]FS
D4BS-4[]FS
Note: There are fluctuations in the contact ON/OFF timing for 2NC contacts. Confirm performance before application.
* Conduit outlet
D4BS-1[]FS :Pg 13.5
D4BS-2[]FS :G1/2
D4BS-4[]FS: M20
Operation Keys
D4BS-K1
D4BS-K2
D4BS-K3
With Operation Key Inserted
D4BS + D4BS-K1
D4BS + D4BS-K2
D4BS + D4BS-K3
Note: Unless otherwise specified, a tolerance of ±0.4 mm applies to all dimensions.
*1. The insertion radii apply when the rotational center of the Operation Key in on surface A in the figures.
*2. The insertion radii apply when the rotational center of the Operation Key in on the Operation Key installation surface.
Features | Safety Door Switches – D4BS series
- Wide temperature range specifications: -40 to 80°C
- Degree of protection of the switch box: IP67
- Conforms to ISO 14119
Properties | Safety Door Switches – D4BS series
Safety Door Switches | D4BS |
---|---|
Direct opening force | 19.61 N |
Max Actuation Frequency | 30 operations / min |
Max Actuation | 500 mm / s |
Weight | Approx. 285 g |
Built-in Switch | 1 NO/1 NC, 2 NC (Slow-action) |
Degree of protection | IP67 |
Dimensions (W x L x H) mm | 111.5 x 40 x 43 |